  • Solid-State Timer H3Y-2, DC Power Source

Solid-State Timer H3Y-2, DC Power Source H3Y-2 DC12 30S

5.00 (4)
H3Y-2 DC12 30S
Package Qty.
Ship pack of
45.43 SGD
In stock
Now we ship to...
...see all
Item Feature
This product is manufactured in Japanese standards. Please check the specification before you order.
Operating Temperature Range (deg C)
Power Supply Voltage (V)
External Dimensions (Width (W)x Depth (D)x Height (H)) (mm)
Below 21.5 x 63 x below 28
Opreration Method
Limited-time operation
Maximum Time Scale
Terminal Shape
Plug-in (surface mounting) 8 pin
Reset Method
Self recovery
Vibration Resistance
10 to 55Hz single amplitude 0.75mm each 1h 3-way
Voltage Influence
+/-2% or less (with full-scale time)
Operating Ambient Temperature (deg C)
-10 to +50 (however, no freezing)
Protection Structure
-10 to +55 (however, no freezing)
Electrical Life
More than 10 million times (no load, switching frequency of 1800 times/h)
Storage Temperature (DegreeC)
-25 to 65 (however, no freezing)
Noise Immunity
Square wave noise by noise simulator (pulse width of 100ns/1micros rise 1ns) +/-1.5kV
Set Error
+/-10% +/-50ms or less (with full-scale time)
Impact Resistance (Malfunction)
100 m/s2 6 direction 3 times each
Vibration Resistance (malfunction)
10 To 55Hz cantilever amplitude of 0.5mm 3-direction each 10min
Withstand Voltage
Conductive terminal and exposed non-charging metal spacing (excluding terminal screw part): AC2000V 50/60Hz 1min Between operation power supply circuit and system control output : AC2000V 50/60Hz 1min Point of contact between unlike poles: AC2000V 50/60Hz 1min Point of contact between discontinuity:AC1000V 50/60Hz 1min
Time Limit Contact
Operating Mode
Power-on delay
Ambient Humidity
35 - 85%
Electrostatic Yield Strength
4kV (malfunction), 8kV (breakage)
Time Specification
1s - 30s
Release Voltage
More than 10% of the supply voltage
Weight (g)
About 50
Impulse Voltage(V)
Power terminal spacing: 1k Conductive terminal and exposed non-charging metal spacing: 1.5k
Operating Time Variation
+/-1% or less (with full-scale time)
Insulation Resistance (Mohm)
More than 100 (measured with DC500V mega)
Control Output
AC250V 5A resistance load (cosphi =1) Minimum applied load DC5V 1mA (P standard and reference values)
Effect of Temperature
+/-2% or less (with full-scale time)
Electrical Service Life (rated load)
More than 500,000 (AC250V 5A resistance load switching frequency 1800 times/h) (at room temperature)
Recovery Time
0.1s or less (including recovery on the way)
Power Consumption
Before time-up : About 0.1W After time-up : About 1.1W (at DC12V)
Allowable Voltage Range(V)
90 to 110% of power supply voltage Continuous use at 50degreeC temperature range uses 95 to 110% of the supply voltage
Impact Resistance
1000 m/s2 6 way 3 times each
Customer Reviews
5 star 4
4 star 0
3 star 0
2 star 0
1 star 0
Review Rating: 5.00
4 Customer Reviews
The reviews are automatic translation.
LED stop lamp blinks timer setting time, was to then switch to light up
From Japan
On 2016-05-04 20:17:19
Amount of money, are satisfied with the quality. Profession because "maintenance of equipment." Omron products are accustomed to handle, easy to use.
This review is about item#02089236.
Timer of the work machine of the pump
From Japan
On 2015-06-29 19:16:57
Compact may be. Set easy to be, it will be saved.
This review is about item#02089202.
Sequence change of power equipment
From Japan
On 2013-12-22 18:04:35
Mmm ... Was the Omron product normally! Of course, the operation down pat! !
This review is about item#02089324.
12 volt use in battery power supply control
From Japan
On 2013-11-06 22:42:26
We are satisfied about the product, but because it does not come with detailed instructions, have been struggling to mounting. I want you to put even manual is the next time you buy.