NoteBuy more than* S$150* and get FREE SHIPPING

  • Solid-State Timer H3Y-4, DC Power Source

Solid-State Timer H3Y-4, DC Power Source H3Y-4 DC24 10S

5.00 (2)
H3Y-4 DC24 10S
Package Qty.
Ship pack of
46.70 SGD
In stock
Now we ship to...
...see all
Item Feature
This product is manufactured in Japanese standards. Please check the specification before you order.
Protection Structure
Instantaneous Contact
Electrostatic Yield Strength
Malfunction: 4 kV 8 KV breakdown:
Time Specification
0.5s - 10s
Operating Temperature Range (deg C)
-10 to +55 (however, no freezing)
Weight (g)
About 50
Mechanical: More than 10 million times (no load, switching frequency of 1800 times/h) Electrical: more than 200000 (AC250V3A resistance load switching frequency 1800 times/h) at room temperature
Control Output
Type: limited time relay 4 c Contact output switching capacity (resistive load (cos phi = 1)): AC 250 V3A, minimum applied load :DC1V1mA (P levels and reference values)
Vibration Resistance (malfunction)
10 To 55Hz cantilever amplitude of 0.5mm 3-direction each 10min
Impulse Voltage(V)
Power terminals 1 kV Non-rechargeable metal across exposed conductive power of PIN and :1.5kV
Recovery Time
0.1s or less (including recovery on the way)
Impact Resistance
1000 m/s2 6 way 3 times each
Vibration Resistance
10 to 55Hz single amplitude 0.75mm each 1h 3-way
Time Limit Contact
Insulation Resistance (Mohm)
More than 100 (with DC500V mega)
Power Supply Voltage (V)
Maximum Time Scale
Power on delay
Effect of Temperature
+/-2% or less (Percentage of the maximum scale value)
Voltage Influence
+/-2% or less (Percentage of the maximum scale value)
Impact Resistance (Malfunction)
100 m/s2 6 direction 3 times each
Withstand Voltage
Conductive terminal and exposed non-charging metal spacing (excluding terminal screw part): AC2000V 50/60Hz 1min Between operation power supply circuit and system control output : AC2000V 50/60Hz 1min Different pole contact between :AC1500V50/60 Hz 5 min
Noise Immunity
Square wave noise by simulator (pulse width of 100 ns/1 micro s rise 1 ns) +/- 1.5 kV
Set Error
+/- 10% +/- 50 ms or less (as a percentage of maximum scale value)
Operating Time Variation
+/-1% or less (rate over a full scale)
Customer Reviews
5 star 2
4 star 0
3 star 0
2 star 0
1 star 0
Review Rating: 5.00
2 Customer Reviews
The reviews are automatic translation.
Training kit to be used in the training
From Japan
On 2016-07-15 16:33:53
Since Omron has been used without any problems.
This review is about item#02490537.
Because of the control panel to create
From Japan
On 2015-04-21 15:59:28
Very, easy-to-use. However, the price is slightly higher is I think the disadvantages.
This review is about item#02490537.