NoteBuy more than* S$200* and get FREE SHIPPING

  • General-Purpose Relay LY3
  • General-Purpose Relay LY3
  • General-Purpose Relay LY3

General-Purpose Relay LY3 LY3N AC200/220

5.00 (2)
Item.#
02492296
Mfr.#
LY3N AC200/220
Package Qty.
1PC
Ship pack of
1
22.43 SGD
ADD TO CART
In stock
Now we ship to...
...see all
Item Feature
Caution
This product is manufactured in Japanese standards. Please check the specification before you order.
Failure Rate P Level (Reference Value: Opening/Closing Frequency 120 times/min)
DC5V 100mA
Maximum Switching Frequency (times/hour)/mechanical
18000
Rated Current
10A
Inductive Load (cos phi =0.4, L/R = 7 ms)
AC110V 7.5A
Impact Resistance (Malfunction)
200m/s2
Weight (g)
About 50
Release Voltage
More than 30 %
Coil Inductance (H)/ Iron Opening Time
Reference value: 34.8 (60 Hz)
CR Circuit
Not available
Terminal Shape
Plug-in terminal
Diode
Not available
Rated Voltage (V)
AC200/220
Indicator Lamp
Available
Electrical Durability
More than 200,000 (rated openign and closing frequency of 1800 times per hour)
Contact Resistance (mohm)
Less than 50 DC5V 1A voltage depression
Vibration Resistance (malfunction)
10-55 To 10 Hz single amplitude (double amplitude of 1.0 mm) 0.5 mm
External Dimensions (Width (W)x Depth (D)x Height (H)) (mm)
31.5 or less x 42.9 x 28.0 or less
Recovery Time
25 ms or less Rated operation voltage condition, excluding contact bounce.
Operating Time
25 ms or less Rated operation voltage condition, excluding contact bounce.23 deg C ambient temperature
Coil Resistance (ohm)
reference value: -- 8650 (coil temperature o'clock of 23 deg C, 60 Hz) common-difference:-[ +15% of ] 20%
Rated Current (mA)
reference value: -- 50 Hz:9.0/10.0 60-Hz:7.7 / 8.5 (coil temperature o'clock of 23 deg C) common difference:-[ +15% of ] 20%
Contact Type
Single
Maximum Switching Frequency (times/hour)/rated load
1800
Operating Voltage
80% or less
Number of Poles
3
Form
LY3N
Resistance Load
AC110V 10A
Maximum Contact Voltage (V)
AC250
Coil Inductance (H)/ Iron Working Time
Reference value: 59.5 (60 Hz)
Ambient Humidity
5 - 85%RH
Impact Resistance
1000m/s2
Contact Materials
AgCdO
Power Consumption (VA, W)
About 1.6-2.0
Number of Pins
11
Installation Shape
Standard type
Mechanical Durability
More than 50 million (18,000 annual opening and closing frequency/h)
Operating Ambient Temperature (deg C)
-25 To 55 (not in cases of freezing or condensation ) Live 4 1a current is -25 to 70 degree c
Insulation Resistance (Mohm)
More than 100 Measure the same DC500V insulation resistance meter for voltage section location
Maximum Voltage (V)
110% (ambient temperature of 23 deg C)
Classification
Operating display light built-in type
Contact Maximum Value
Resistive load: 10A Inductive load: 10A
Withstand Voltage
Coil and contacts between :AC2000V50/60 Hz 5 min Different pole contacts between :AC2000V50/60 Hz 5 min The junction between same poles :AC1000V50/60 Hz 5 min
Vibration Resistance
10-55 To 10 Hz single amplitude (double amplitude of 1.0 mm) 0.5 mm
Customer Reviews
5 star 2
4 star 0
3 star 0
2 star 0
1 star 0
Review Rating: 5.00
2 Customer Reviews
The reviews are automatic translation.
Relay exchange of foundation of the operating device
5
From Japan
On 2015-12-22 10:04:16
Not rarely break things, but skilled in the art to which repair sale was in trouble what to do because it is out of business, was saved by there same products.
This review is about item#02492296.
Use the control panel for the vacuum pipe valve control
5
From Japan
On 2015-03-17 13:32:26
You can use without any problem as expected. I feel truly Do's Omron's products.
This review is about item#02492287.