Buy more than* S$200* and get FREE SHIPPING

  • Uninterruptible Power Supply BX Series
  • Uninterruptible Power Supply BX Series
  • Uninterruptible Power Supply BX Series
  • Uninterruptible Power Supply BX Series

Uninterruptible Power Supply BX Series BX50FW

Item.#
08592017
Mfr.#
BX50FW
Package Qty.
1PC
Ship pack of
1
373.39 SGD
ADD TO CART
In stock
Now we ship to...
...see all
Item Feature
Caution
This product is manufactured in Japanese standards. Please check the specification before you order.
Backup Time
3.5 minutes or more
Starting Voltage Range (V)
100V mode: AC86 +/-4 - 114 +/-4, 110V mode: AC96 +/-4 - 124 +/-4 115V mode: AC101 +/-4 - 129 +/-4, 120V mode: AC106 +/-4 - 134 +/-4
Charging Time (hours)
12
Switching Time (sec)
Within 10m
Lifespan
If five years (long life) ambient temperature 20deg C - 4: expected
Output Capacity
(Both upper limit) 500VA/300W
Battery
Sealed lead-acid battery: DC6V/7.2Ahx2 pieces
Output Waveform
Commercial time: sine wave / back-up: Tankatachi-ha
Input Plug
3P(NEMA 5-15P)
Functions
Automatic battery check function
Noise Level (dB)
(The 45 following backup operation and UPS start-up) 40 or less
Power Cord (m)
About 1.8
Rated Input Voltage (V)
AC100/110/115/120
Rated Current (A)
5
Output Voltage
100V mode:: AC100V -10 / +10 V, 110V mode: AC110V -10 / +5 V, 100V mode: AC115V -10 / +5 V, 120V mode: AC115V - Commercial operation: input voltage through output backup operation If you are using the 10 / +5 V AC100V other modes, please check t
Power Consumption (W)
10/20 up to normal
Height (mm)
Rubber feet: about 2.5
Specification
Battery replacement: User side can replace hot swap. Setting vertical and horizontal is available.
Calorific Value (KJ/h)
72, 122 at the time of charging the normal time
Input Protection Capacity (A)
15
Input Voltage Tolerance (V)
100V mode: AC86 +/-4 - 114 +/-4, 110V mode: AC96 +/-4 - 124 +/-4 115V mode: AC101 +/-4 - 129 +/-4, 120V mode: AC106 +/-4 - 134 +/-4
Input Frequency (Hz)
50/60 +/-4
Protection Feature
Input: Reset type overcurrent protection device overload: stop alarm output at the rated capacity or more, on an ongoing 5 minutes or more, the output droop (backup operation) power noise / lightning surge protection
Phase Number
Input: single-phase 2-wire, output: single-phase two-wire
Humidity Range
(That of the storage battery fully charged, with no condensation) RH 90% - 10: -: use environment 25 85% RH (non-condensing) storage environment
Interface
Serial communication (RS232C): D-sub9 pin contact signal input and output simultaneous disabled
Output Frequency (Hz)
Commercial operation: input frequency through output backup operation: 50/60 +/-1
Outlet Output
5-15Rx2 or NEMA: backup
Cooling System
Natural air cooling
External Dimensions (Width (W)x Depth (D)x Height (H)) (mm)
287x287x45 (+/-1)
Operating Method
Commercial power supply system at all times
Maximum Current (A)
12
OS Support
PowerAct Pro: Windows Server 2003 x64 Editions / XP Professional x64 Edition / Server 2003/XP/Me/98, Linux UPS service driver: Windows Server 2003 x64 Editions / XP Professional x64 Edition / Server 2003/XP/2000, Linux for the OS of Japanese / E
Temperature Range (deg C)
Use Environment: 0 - 40, Storage environment: -15 - 40
Standard
Noise regulations (standards compliant): VCCI Class B safety / RoHS Directive: UL1778/CE/RoHS corresponding power cable: UL Standard Certified
Weight (kg)
About 5
Accessories
Stand, 3P-2P conversion plug, connecting cable (RS232C about 2.2m) x1 this software (network-enabled automatic shutdown software PowerAct Pro, UPS service driver software) vertical